Siemens SIMATIC S7-300 Reference Manual page 245

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

4.7
Analog module parameter assignment
Introduction
Analog modules can have different characteristics. You can set the characteristics
of the modules by means of parameter assignment.
Tools for parameter assignment
You assign parameters to analog modules with STEP 7. You must perform
parameter assignment in STOP mode of the CPU.
When you have set all the parameters, download the parameters from the
programming device to the CPU. On a transition from STOP to ³ RUN mode, the
CPU then transfers the parameters to the individual analog modules.
In addition, if necessary you must place the measuring range modules of the
module in the necessary position (refer to Section 4.4).
Static and dynamic parameters
The parameters are divided into static and dynamic parameters.
Set the static parameters in STOP mode of the CPU, as described above.
You can similarly modify the dynamic parameters in the current user program by
means of SFCs. Note, however, that after a change from RUN ³ STOP, STOP ³
RUN of the CPU, the parameters set in STEP 7 apply again. You will find a
description of the parameter assignment of modules in the user program in
Appendix A.
Parameter
Static
Dynamic
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Settable with
PG (STEP 7 HW CONFIG)
PG (STEP 7 HW CONFIG)
SFC 55 in the user program
Analog Modules
CPU Operating
State
STOP
STOP
RUN
4-39