hit counter script

Calculation Of The Filter And Processing Time - Siemens SIMATIC S7-300 Reference Manual

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Analog Modules

Calculation of the filter and processing time

Independent of the number parameterized channels, the same time conditions are
always valid. The time related to the clock signal for the reading of a specific
channel is calculated according to the formula:
T
_CH = (Channel number +1) x 52 ms + tv; tv = 119 to 209 ms
WE
CH7
52ms 52ms
Figure 4-38
Explanation of the mode of operation in synchronous operation
The module begins with the A/D conversion of channel 7 and saves this result
internally. Then channels 6...0 are converted sequentially at intervals of 52 ms in
the same way. After a further internal processing time the result becomes available
to all converted channels at the backplane bus for collection by the CPU.
Further information
Further information on synchronicity can be found in the Online help of STEP 7, in
the manualLocal peripheral system ET 200M and in the manual Synchronicity.
4-102
A/D conversion
CH6
CH5
CH4
CH3
52ms
52ms
52ms
Calculation of the filter and processing time
T
WE
internal processing (tv)
CH2
CH1
CH0
52ms
52ms
52ms
Programmable Logic Controllers S7-300 Module Data
209ms
A5E00105505-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF