hit counter script

A-26 Codes For The Measuring Ranges Of The Sm 331; Ai 8 X16 Bits - Siemens SIMATIC S7-300 Reference Manual

Programmable logic controllers module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Module modes
Table A-24 contains the codes for the module modes, which you enter in byte 0 of
data record 128 (see Figure A-14).
Table A-24 Codes for the modes of SM 331; AI 8 x 16 bits
Interference suppression
Table A-25 contains the codes for the different frequencies, which you enter in byte
1 of data record 128 (see Figure A-14). Note that 4-channel mode only functions if
interference frequency suppression of 50, 60 and 400 Hz is set.
Table A-25 Codes for interference frequency suppression of the SM 331; AI 8 x 16 bits
Interference Suppression
Measuring methods and measuring ranges
Table A-26 contains all the measuring ranges for the isolated analog input module
SM 331; AI 8 x 16 bits. Table A-26 also shows the codes for measuring methods
and measuring ranges. You must enter these codes in accordance with the
required measuring range in the relevant byte of data record 128
(see Figure A-14).
Table A-26 Codes for the measuring ranges of the SM 331; AI 8 x16 bits
Measuring Method
Deactivated
Voltage
Current (4-wire transmitter)
Settings for input smoothing
Table A-27 contains all the smoothing settings for the isolated analog input module
SM 331; AI 8 x 16 bits. According to the smoothing required, you must enter these
codes in the corresponding byte of data set 128 (see imag eA-14.
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Module mode
8 channels
4 channels
400 Hz
60 Hz
50 Hz
50, 60 and 400 Hz
Code
2#0000
2#0001
2#0002
Parameter Sets for Signal Modules
2#00000000
2#00000001
Measuring Range
Deactivated
± 5 V
1 to 5 V
± 10 V
0 to 20 mA
4 to 20 mA
± 20 mA
Code
Code
2#00
2#01
2#10
2#11
Code
2#0000
2#0110
2#0111
2#1001
2#0010
2#0011
2#0100
A-35