Notes on the table
There is a separate table for each manual that describes the technical
specifications of the signal modules of the S7-300 product family.
The "Behavior of the Inputs/Outputs" column indicates the behavior of the
inputs/outputs when reparameterization is carried out in RUN mode, provided they
are not affected by reparameterization.
Module
S7-300 module specifications
6ES7 321-7BH00-0AB0
6ES7 321-7BH80-0AB0
SM 321; DI 16 DC 24 V;
with hardware interrupt and
diagnostic interrupt
6ES7 321-7BH01-0AB0
SM 321; DI 16 DC 24 V;
with hardware interrupt and
diagnostic interrupt, clocked
6ES7 322-8BF00-0AB0
6ES7 322-8BF80-0AB0
SM 322; DO 8 DC 24 V/
0.5 A; with diagnostic
interrupt
6ES7 322-5FF00-0AB0
SM 322;DO 8 AC 120/230V/
2A ISOL
6ES7 322-5HF00-0AB0
SM 322;
DO 8 Rel. AC 230V/5A
6ES7 331-7NF00-0AB0
SM 331; AI 8 16 Bit
6ES7 331-7NF10-0AB0
SM 331; AI 8 16 Bit
6ES7 331-7PF00-0AB0
SM 331; AI 8 RTD
6ES7 331-7PF10-0AB0
SM 331; AI 8 TC
Product Information on the Manual
A5E00201782-02
Behavior of the
inputs/outputs
Supply the last valid
process value before
parameterization
Output the last valid
output value before
output value before
parameterization
Supply the last valid
process value before
parameterization
parameterization
Peculiarities when reparameterizing
---
---
---
SF LED shines:
If there was a pending diagnosis before
reparameterization, the SF LEDs (on the
reparameterization, the SF LEDs (on the
CPU, IM, or module) may still be shining
CPU, IM, or module) may still be shining
although there is no longer a pending
diagnosis and the module is working
correctly.
correctly.
Remedy:
•
Only reparameterize when there is no
pending diagnosis on the module, or
pending diagnosis on the module, or
•
Remove the module, and then plug it in
again
3