RS 485 Repeater
7.1
Application and Characteristics;
(6ES7972-0AA01-0XA0)
Order number
6ES7972-0AA01-0XA0
What is an RS 485 repeater?
The RS 485 repeater amplifies data signals on bus lines and interconnects bus
segments.
Application of the RS 485 repeater
You need an RS 485 repeater if:
• More than 32 nodes are connected to the bus
• Bus segments are to be operated non-grounded on the bus, or
• The maximum cable length of a segment is exceeded. (See table 7-1).
Table 7-1
Baud Rate
9.6 to 187.5 kbd
500 kbaud
1.5 Mbaud
3 to 12 Mbaud
Rules
If you configure the bus with RS 485 repeaters:
• Up to 9 RS 485 repeaters can be connected in series.
• The maximum cable length between two nodes must not exceed the values in
Table 7-2.
Table 7-2
Baud Rate
9.6 to 187.5 kbaud
500 kbaud
1.5 Mbaud
3 to 12 Mbaud
7-2
Maximum Cable Length of a Segment
Maximum Cable Length between Two RS 485 Repeaters
Maximum Length of Cable between 2 Nodes (in m) with
Max. Cable Length of a Segment (in m)
1000
400
200
100
RS 485 Repeater (6ES7972-0AA01-0XA0)
10000
4000
2000
1000
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03