System
Decimal
Hexadecimal
-27649
93FF
-32512
8100
-32513
80FF
-32768
8000
Table A- 219 Analog input representation for current (SB and SM)
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-4864
ED00
-4865
ECFF
-32768
8000
A.12.3.4
Measurement ranges of the analog outputs for voltage and current (SB and SM)
Table A- 220 Analog output representation for voltage (SB and SM)
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
Voltage Measuring Range
±10 V
±5 V
-11.759 V
-5.879 V
-11.851 V
-5.926 V
0 mA to 20 mA
23.70 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
-3.52 mA
± 10 V
See note 1
See note 1
11.76 V
10 V
7.5 V
361.7 μ V
0 V
-361.7 μ V
-7.5 V
-10 V
A.12 Analog signal boards (SBs)
±2.5 V
±1.25 V
-2.940 V
-1.470 V
-2.963 V
-1.481 V
Current measuring range
4 mA to 20 mA
22.96 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
Voltage Output Range
Overflow
Overshoot range
Rated range
Technical specifications
Undershoot range
Underflow
Overflow
Overshoot range
Nominal range
Undershoot range
Underflow
951