Technical specifications
A.8 Analog signal modules (SMs)
Table A- 144 Connector pin locations for SM 1231 AI 4 x 16 bit (6ES7 231-5ND30-0XB0)
Note
Unused voltage input channels should be shorted.
Unused curent input channels should be set to the 0 to 20 mA range and/or disable broken
wire error reporting.
Inputs configured for current mode will not conduct loop current unless the module is
powered and configured.
Current input channels will not operate unless external power is supplied to the transmitter.
A.8.2

SM 1232 analog output module specifications

Table A- 145 General specifications
Technical data
Order number
Dimensions W x H x D (mm)
Weight
Power dissipation
Current consumption (SM Bus)
Current consumption (24 VDC)
Table A- 146 Analog outputs
Technical data
Number of outputs
Type
Range
Resolution
910
Pin
X10 (gold)
1
L+ / 24 VDC
2
M / 24 VDC
3
GND
4
AI 0+
5
AI 0-
6
AI 1+
7
AI 1-
SM 1232 AQ 2 x 14 bit
6ES7 232-4HB32-0XB0
45 x 100 x 75
180 grams
1.8 W
80 mA
45 mA (no load)
SM 1232 AQ 2 x 14 bit
2
Voltage or current
±10 V, 0 to 20 mA, or 4 mA to 20
mA
Voltage: 14 bits
Current: 13 bits
X11 (gold)
No connection
No connection
No connection
AI 2+
AI 2-
AI 3+
AI 3-
SM 1232 AQ 4 x 14 bit
6ES7 232-4HD32-0XB0
45 x 100 x 75
180 grams
2.0 W
80 mA
45 mA (no load)
SM 1232 AQ 4 x 14 bit
4
Voltage or current
±10 V, 0 to 20 mA, or 4 mA to 20
mA
Voltage: 14 bits
Current: 13 bits
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG