Technical data
Input impedance
Differential
Common mode
Behavior on RUN to STOP
Measuring principle
Common mode rejection
Operational signal range
Isolation (field side to logic)
Cable length (meters)
Table A- 208 Diagnostics
Technical data
Overflow/underflow
24 VDC low voltage
Table A- 209 Wiring diagram for the analog input SB
SB 1231 AI x 12 bit (6ES7 231-4HA30-0XB0)
Connect "R" and "0+" for current
Note: Connectors must be gold. See Appendix C, Spare Parts for order number.
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
SB 1231 AI 1x12 bit
Voltage: 220 kΩ; Current: 250 Ω
Voltage: 55 kΩ; Current: 55 kΩ
Last value or substitute value (default value 0)
Actual value conversion
400 dB, DC to 60 Hz
Signal plus common mode voltage must be less than +35 V and
greater than -35 V
None
100 m, twisted and shielded
SB 1231 AI 1 x 12 bit
Yes
no
Technical specifications
A.12 Analog signal boards (SBs)