TSEND_C and TRCV_C Error and Status condition codes
ERROR
STATUS
0
0000
0
7000
0
7001
0
7002
0
7003
0
7004
1
8085
1
8086
1
8087
1
8088
1
8089
1
8091
1
809A
1
809B
1
80A1
1
80A3
1
80A4
1
80A5
1
80A7
1
80B2
1
80B3
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
Description
Job executed without error
No job processing active
Start job processing, establishing connection, waiting for connection partner
Data being sent or received
Connection being terminated
Connection established and monitored, no job processing active
LEN parameter is greater than the largest permitted value.
The CONNECT parameter is outside the permitted range.
Maximum number of connections reached; no additional connection possible.
LEN parameter is not valid for the memory area specified in DATA.
The CONNECT parameter does not point to a data block.
Maximum nesting depth exceeded.
The CONNECT parameter points to a field that does not match the length of the
connection description.
The local_device_id in the connection description does not match the CPU.
Communications error:
The specified connection was not yet established
•
The specified connection is currently being terminated; transmission over this
•
connection is not possible
The interface is being reinitialized
•
Attempt being made to terminate a nonexistent connection
IP address of the remote partner connection is invalid. For example, the remote partner
IP address is the same as the local partner IP address.
Connection ID (Page 514) is already in use.
Communications error: You called TDISCON before TSEND_C was complete.
The CONNECT parameter points to a data block that was generated with the keyword
UNLINKED.
Inconsistent parameters:
Error in the connection description
•
Local port (parameter local_tsap_id) is already present in another connection
•
description.
ID in the connection description different from the ID specified as parameter
•
Communication
10.2 PROFINET
525