Table 12- 32 Data types for parameters
Parameter and type
REQ
IN
PORT
IN
SIGNAL
IN
RTS
IN
DTR
IN
DSR
IN
DONE
OUT
ERROR
OUT
STATUS
OUT
Table 12- 33 Condition codes
STATUS (W#16#....)
80F0
80F1
80F2
80F3
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
Data type
Description
Bool
Start the set RS232 signals operation, on the rising edge of this input
(Default value: False)
PORT
After you install and configure a CM or CB communication device, the
port identifier appears in the parameter helper drop-list available at the
PORT box connection. The assigned CM or CB port value is the device
configuration property "hardware identifier". The port symbolic name is
assigned in the "System constants" tab of the PLC tag table. (Default
value: 0)
Byte
Selects which signal to set: (multiple allowed). Default value: 0
01H = Set RTS
•
02H = Set DTR
•
04H = Set DSR
•
Bool
Request to send, module ready to send value to set (true or false),
Default value: False
Bool
Data terminal ready, module ready to send value to set (true or false).
Default value: False
Bool
Data set ready (only applies to DCE type interfaces), not used.
Bool
TRUE for one execution after the last request was completed with no
error
Bool
TRUE for one execution after the last request was completed with an
error
Word
Execution condition code (Default value: 0)
Description
CM or CB is RS485 and no signals can be set
Signals cannot be set because of Hardware flow control
Cannot set DSR because module is DTE
Cannot set DTR because module is DCE
Communication processor and Modbus TCP
12.3 Point-to-point (PtP) communication