During the execution of the command for drive-controlled homing (C0600)
an error was detected.
Cause:
The evaluation of the home switch has been switched on (S-0-0147,
Homing parameter). The distance between selected home switch edge
and reference mark to be evaluated is outside the allowed range.
Remedy:
Read the value from parameter S-0-0298, Reference cam shift and take
it over to parameter S-0-0299, Home switch offset
- or -
shift the reference cam.
See also Functional Description "Establishing Position Data Reference for
Relative Measuring Systems"