hit counter script

Connecting Power To The Cisco Asr 1006 Router - Cisco ASR 1013 Hardware Installation Manual

Asr 1000 series
Hide thumbs Also See for ASR 1013:
Table of Contents

Advertisement

Cisco ASR 1006 Router Overview and Installation

Connecting Power to the Cisco ASR 1006 Router

The covers are an integral part of the safety design of the product. Do not operate the unit without the
Warning
covers installed. Statement 1077
When you install the unit, the ground connection must always be made first and disconnected last. Statement
Warning
1046
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Warning
Statement 1003
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Warning
Statement 1030
This section describes the procedure to connect AC input and DC input power to your Cisco ASR 1006 Router.
The DC power supply for the Cisco ASR 1006, ASR 1004, ASR 1002, and ASR 1013 routers operate at
individual specifications. The following table shows the common input ranges and circuit breaker requirements.
Table 48: Cisco ASR 1000 Series Router DC Power Supply System Input Requirements
Cisco ASR 1000
System Input Rating
Series Router DC
(Amps)
Power Supply
Cisco ASR 1006
40
Cisco ASR 1004
24
Cisco ASR 1002
16
Cisco ASR 1013
40
Circuit Breaker
AWG # Wire
Amps
Minimum
Maximum
Always 50
Always AWG #6
wire
30
40
20
30
Always 50
Always AWG #6
wire
Cisco ASR 1000 Series Router Hardware Installation Guide

Connecting Power to the Cisco ASR 1006 Router

Minimum
Maximum
10
8
12
10
165

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents