7.5
Refresh Parameters
Set link refresh ranges between the link devices of the master/local module and the devices of the CPU module.
(1) Setting procedure
1.
Set network setting parameters. (
2.
Open the setting window.
Project window
3.
Set parameters in the window.
4.
Click the
Item
Select a link device assignment method.
Assignment Method
• Points/Start: Enter the points and start numbers of link devices.
• Start/End: Enter the start and end numbers of link devices.
Set the link refresh ranges of SB and SW. One range can be set for
each SB and SW. (
Dev. Name
Transfer SB
Transfer
SW
Points,
Start, End
[Parameter]
button
button.
Description
Page 127, Section 8.1.2)
Ex.
0000
H
Device
name
(SB)
01FF
H
0000
H
Device
name
(SW)
01FF
H
Master/local module
Page 84, Section 7.2)
[Network Parameter]
[Ethernet/CC IE/MELSECNET]
Transfer
0000
H
SB
Device
name
(SB)
01FF
H
Transfer
0000
H
SW
Device
name
(SW)
01FF
H
CPU module
CHAPTER 7 PARAMETER SETTING
Setting range
• Points/Start
• Start/End
(Default: Start/End)
(1)
Transfer SB
• Link Side: Fixed at "SB".
• PLC Side: M, L, B, D, W, R, SB, ZR
(2)
Transfer SW
• Link Side: Fixed at "SW".
• PLC Side: M, L, B, D, W, R, SW, ZR
(Default: Blank)
• Link Side: 0 to 1FF
H
• PLC Side: Within device range of
CPU module
(Default: Blank)
Set bit devices in increments of 16
points and word devices in increments
of 4 points.
7
103