Device
Item
Total number of
(S1)+2
slave stations
Constant link scan
(S1)+3
time
(S1)+4
IP address (network
address)
(S1)+5
366
• For a master station and submaster station
Set the number of connected slave stations (needs to be set for a master
station).
To use areas for a master station when using the submaster function, set "the
number of connected slave stations + 1".
• For local stations
This item needs not to be set.
• For a master station and submaster station
Specify constant link scan time (needs to be set for a master station).
0: No setting
1 to 200: Constant link scan time (unit: ms)
• For local stations
This item needs not to be set.
• For a master station and submaster station
When using the IP packet transfer function, set the first and second octets of
the IP address of the master/local module (master station and submaster
station only). (
Page 148, Section 8.3.2)
(S1) + 5
Network address
• For local stations
This item needs not to be set.
Setting data
(S1) + 4
Dummy
Setting
Set by
range
1 to 120
(1 to 121
when the
User
submaster
function is
used)
0 to 200
User
0 to 255
User