Item
Dev. Name
Transfer 1
to 256
Points,
Start, End
button
104
Description
Set the link refresh ranges of RX, RY, RWr, and RWw. Up to 256
ranges can be set. (
Page 127, Section 8.1.2)
Ex.
0000
H
Device
name
(RX)
00FF
H
0000
H
Device
name
(RY)
00FF
H
0000
H
Device
name
(RWr)
00FF
H
0000
H
Device
name
(RWw)
00FF
H
Master/local module
Reset refresh parameters to default.
Transfer
1000
H
1
Device
name
(X)
10FF
H
Transfer
1000
H
2
Device
name
(Y)
10FF
H
Transfer
000000
H
3
Device
name
(W)
0000FF
Transfer
001000
H
4
Device
name
(W)
0010FF
CPU module
Setting range
• Link Side: RX, RY, RWr, RWw
• PLC Side:
When RX is set to "Link Side":
X, M, L, B, D, W, R, ZR
When RY is set to "Link Side":
Y, M, L, B, T, C, ST, D, W, R, ZR
When RWr is set to "Link Side":
M, L, B, D, W, R, ZR
When RWw is set to "Link Side":
M, L, B, T, C, ST, D, W, R, ZR
(Default: Blank)
• Link Side:
0 to 3FFF
for RX/RY
H
0 to 1FFF
for RWr/RWw
H
H
• PLC Side: Within device range of
CPU module
H
(Default: Blank)
Set bit devices in increments of 16
points and word devices in increments
of 4 points.