Zp.remto (Writing Data To The Intelligent Device Station/Remote Device Station) - Mitsubishi Electric QJ71GF11-T2 User Manual

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

10.14
ZP.REMTO (Writing Data to the Intelligent Device Station/
Remote Device Station)
This instruction writes data to the buffer memory of the intelligent device station/remote device station. (In units of
words)
ZP.REMTO
Setting
Internal device
*1
(System, user)
data
Bit
Word
n1
n2
n3
n4
(S)
n5
D
*1
Local devices and file registers set for each program cannot be used.
(1) Setting data
Setting data
"Jn"/Jn
n1
n2
n3
n4
S
n5
D
338
Start contact
ZP.REMTO
Link direct device
File
J\
register
R, ZR
Bit
Word
Description
Target network No. (1 to 239)
Channels used by own station (1 to 32)
Target station No. (1 to 120)
• Remote head module or head module
The start I/O number of the intelligent function module
(00 to FE
: Upper two digits of the I/O number expressed in three
H
digits)
• Modules other than remote head modules or head modules
Fixed to 00
The start address of the buffer memory of the intelligent device station/
remote device station where data is written
Start device of the own station where data to be written is stored
Number of write points (1 to 240 words)
The device of the own station that turns on for one scan upon
completion of the instruction.
If the instruction fails, (D)+1 also turns on.
Jn
or
n1
n2
n3
"
"
Jn
Available devices
Intelligent function
module device
U\G
n4
(S)
n5
(D)
Constant
Index register
Zn
K, H
$
Set by
Data type
String/16-bit
binary
16-bit binary
User
Device name
16-bit binary
System
Bit
Others