(c) Reserved station specification data (master station (needs to be set) and submaster
station only)
When Reserved station specification data (b1) in Setting flag ((S1)+1) is set to valid, store the slave station
number to be reserved.
Device
Item
Reserved station
(S3)+0 to
*1
(S3)+7
specification
*1
When a station is set as both error invalid station and reserved station, the reserved station setting takes priority.
(d) Error invalid station setting data (master station (needs to be set) and submaster
station only)
When Error invalid station setting data (b2) in Setting flag ((S1)+1) is set to valid, store the slave station number
for which error invalid station setting is to be configured.
Device
Item
Error invalid
(S4)+0 to
*1
(S4)+7
station setting
*1
When a station is set as both error invalid station and reserved station, the reserved station setting takes priority.
368
Specify the reserved stations.
0: Not specified (default)
1: Specified
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
(S3)+0
16 15 14 13 12 11 10
(S3)+1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
(S3)+2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
(S3)+3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
(S3)+4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
(S3)+5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
(S3)+6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
(S3)+7
Do not set a submaster station number as a reserved station number. Doing so will cause an
error.
Specify error invalid stations.
0: Not specified (default)
1: Specified
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
(S4)+0
16 15 14 13 12 11 10
(S4)+1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
(S4)+2
(S4)+3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
(S4)+4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
(S4)+5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
(S4)+6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
(S4)+7
Do not set a submaster station number as an error invalid station number. Doing so will cause
an error.
Setting data
9
8
7
6
5
4
120 119 118 117 116 115 114 113
Each number in the table represents station No.
Setting data
9
8
7
6
5
4
120 119 118 117 116 115 114 113
Each number in the table represents station No.
Set by
3
2
1
User
Set by
3
2
1
User