hit counter script

Mitsubishi Electric QJ71GF11-T2 User Manual page 269

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

Device
Item
Target station
(S1)+5
number
(S1)+6
Number of
(S1)+7
resends
Setting data
Specify the target station number.
(1)
Station number specification
Master station: 125 (7D
)
H
Master operating station: 126 (7E
supporting the submaster function (
8))
Local station, intelligent device station, submaster station: 1 to
120
When 125 (7D
) is set, the module always accesses the master
H
station (station number 0). When 126 (7E
submaster function is used, the module accesses the station
operating as a master operating station.
To increase the reliability of data, it is recommended to execute
the instruction with the execution type in (S1)+0 set to "1: With
arrival confirmation".
(2)
Group specification (The target station is on a network other
than CC-Link IE Field Network.)
81
to A0
: All stations in Group No.1 to No.32
H
H
(It can be set when the execution type set for (S1)+0 is "0:
Without arrival confirmation".)
Group No.1: 81
Group No.2: 82
Group No.32: A0
(3)
All stations specification
FF
: All stations on the target station's network No. (excluding
H
the own station)
(It can be set when the execution type set for (S1)+0 is "0:
Without arrival confirmation".)
When using the group specification or all stations specification
• Specify 0000
or 03FF
for the target station's CPU type ((S1)+3)
H
H
(
Page 242, Section 10.2.2 (3))
• The group specification cannot be used for CC-Link IE Field
Network stations.
• Writing of the data cannot be confirmed on the target station. For
whether data was written normally, check the device of the write
target station.
• Data cannot be written to the station with the station number
already in use or the station with no station number setting. Correct
the error then execute the instruction.
Unused
During instruction execution
For the case where the instruction is not completed within the
monitoring time specified by (S1)+8, specify the number of
times the instruction is resent. (It can be set when the execution
type set by (S1)+0 is "1: With arrival confirmation".)
When the instruction is completed
The number of resends performed (result) is stored. (Valid
when the execution type set by (S1)+0 is "1: With arrival
confirmation".)
CHAPTER 10 DEDICATED INSTRUCTIONS
) (only for modules
H
Page 546, Appendix
) is set and the
H
H
H
H
Setting range
Set by
125 (7D
)
H
126 (7E
)
H
1 to 120
User
81
to A0
H
H
FF
H
0
User
0 to 15
User
System
267
10

Advertisement

Table of Contents
loading

Table of Contents