● Descriptions of icons
Click the
button. A brief description of the icon is displayed.
● When multiple master/local modules are mounted on the same base unit
Clicking the
button will change the target module.
● Stations that cannot be selected as a diagnostic target
In the following cases, the status of the corresponding station cannot be checked using the CC-Link IE Field Network
diagnostics.
• The network number of the station differs from those of other stations.
• More than one master station exists in the network.
• The same station number is used for multiple stations.
• More than one submaster station with the same station number exists.
Check the error details by directly connecting the supported programming tool to the slave station in error and opening
the "System Monitor" window. (
CHAPTER 9 CC-LINK IE FIELD NETWORK DIAGNOSTICS
Click.
Page 461, Section 12.6)