Item
Network
Network map
Status
216
Displays the network map of CC-Link IE Field Network and the status of each station.
If the status is not displayed, check that there is only one master station in the system and no
station number is overlapped.
(1)
Icon
The module type and station number are displayed with an icon.
1)
2)
3)
4)
1)
Indicates the station (own station) where GX Works2 is connected.
Displays the network type and station number. "?" is displayed when a station number has not
been set. When the text's background is colored, the relevant station may have been configured
2)
as a reserved station or an error invalid station. Click the
meaning of the background colors.
3)
Shows module status. Click the
4)
Displays a port to which an Ethernet cable is connected.
(2)
Scaling
If all stations are not displayed in the network map, enlarge or reduce the area by pressing
the
key and scrolling the wheel of a mouse. The current zoom size is displayed by
Ctrl
placing the mouse pointer on the network map.
(3)
Network map
A network map is displayed according to the connection status.
Actual system configuration (Star topology)
GX Works2
Master station
(Station No.0)
Intelligent device station
(Station No.3)
Network map
Actual system configuration (Line topology)
GX Works2
Master station
(Station No.0)
Network map
Description
Click Selection
Double-click Displays the "System Monitor" window.
Right-click Executes a test or debugging.
Move the focus to the module to be diagnosed,
and determine it with the
button to check the meaning of the icon.
Switching hub
Intelligent device station
(Station No.4)
Local station
(Station No.1)
keys on the keyboard
key.
Space
button to check the
Intelligent device station
(Station No.5)
Intelligent device station
(Station No.2)

Advertisement