Web server
12.6 Standard Web pages
Note
Be aware of the following issues when using the standard Tag status page:
• Enclose all string modifications in single quotes.
• The Tag status page can monitor and modify tags that contain any of the following
characters: &, <, (, +, ,(comma), ., [, ], $, or %, providing you enclose the tag name in
double quotation marks, for example, "Clock_2.5Hz".
• To monitor or modify just one field of a DTL tag, include the field in the Address, for
example, "Data_block_1".DTL_tag.Year. Enter an integer value for the modify value
according to the data type of the specific field of the DTL. For example, the Year field is a
UInt.
• The maximum number of variable entries per page is 50.
• If a tag name displays special characters such that it is rejected as an entry on the Tag
status page, you can enclose the tag name in double quotation marks. In most cases, the
page will then recognize the tag name.
See also
Rules for entering tag names and values (Page 1084)
1032
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK