Technical data
Settling time
Cable length (meters)
In an overflow condition, analog outputs will behave according to the device configuration properties settings. In the
1
"Reaction to CPU STOP" parameter, select either: "Use substitute value" or "Keep last value".
Table A- 103 Analog output representation for current (CPU 1215C and CPU 1217C)
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
34
22
0
0
Negative values
In an overflow condition, analog outputs will behave according to the device configuration properties settings. In the
1
"Reaction to CPU STOP" parameter, select either: "Use substitute value" or "Keep last value".
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
Description
2 ms
100 m, shielded twisted pair
Current output range
0 mA to 20 mA
See note 1
See note 1
23.52 mA
20 mA
15 mA
0.0247 mA
0 mA
Negative values are not
supported
Overflow
Overshoot range
Rated range
Technical specifications