Table 13- 142 MB_SERVER execution condition codes
STATUS
Response code to
(W#16#)
Modbus server
(B#16#)
7001
7002
7003
8187
818C
8381
01
8382
03
8383
02
8384
03
8385
03
In addition to the MB_SERVER errors listed above, errors can be returned from the
1
underlying T block communication instructions (TCON, TDISCON, TSEND, and TRCV
(Page 857)).
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1
Modbus protocol errors
MB_SERVER is waiting for a Modbus client to connect to the assigned TCP port. This
code is reported on the first execution of a connect or disconnect operation.
MB_SERVER is waiting for a Modbus client to connect to the assigned TCP port. This
code is reported for any subsequent executions, while waiting for completion of a con-
nect or disconnect operation.
A disconnect operation has successfully completed (Only valid for one PLC scan).
Invalid pointer to MB_HOLD_REG: area is too small
Pointer to an optimized MB_HOLD_REG area (must be a non-optimized DB area or M
memory area) or Blocked process timeout exceeds the limit of 55 seconds. (S7-1200
specific)
Function code not supported
Data length error
Data address error or access outside the bounds of the MB_HOLD_REG address area
Data value error
Data diagnostic code value not supported (function code 08)
Communication processor and Modbus TCP
13.8 Legacy Modbus TCP communication
1263