13.4.3.3

USS_Read_Param (Readout parameters from the drive)

Table 13- 47 USS_Read_Param instruction
LAD / FBD
Table 13- 48 Data types for the parameters
Parameter type
REQ
IN
DRIVE
IN
PARAM
IN
INDEX
IN
USS_DB
INOUT
VALUE
IN
DONE
OUT
1
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
SCL
USS_Read_Param(REQ:=_bool_in_,
DRIVE:=_usint_in_,
PARAM:=_uint_in_,
INDEX:=_uint_in_,
DONE=>_bool_out_,
ERROR=>_bool_out_,
STATUS=>_word_out_,
VALUE=>_variant_out_,
USS_DB:=_fbtref_inout_);
Data type
Description
Bool
Send request: When true, REQ indicates that a new read request is de-
sired. This is ignored if the request for this parameter is already pending.
USInt
Drive address: DRIVE is the address of the USS drive. The valid range is
drive 1 to drive 16.
UInt
Parameter number: PARAM designates which drive parameter is written.
The range of this parameter is 0 to 2047. On some drives, the most signif-
icant byte can access PARAM values greater than 2047. See your drive
manual for details on how to access an extended range.
UInt
Parameter index: INDEX designates which Drive Parameter index is to be
written. A 16-bit value where the Least Significant Byte is the actual index
value with a range of (0 to 255). The Most Significant Byte may also be
used by the drive and is drive-specific. See your drive manual for details.
USS_BASE
The name of the instance DB that is created and initialized when a
USS_Drive_Control instruction is placed in your program.
Word, Int, UInt,
This is the value of the parameter that was read and is valid only when
DWord, DInt,
the DONE bit is true.
UDInt, Real
Bool
When true, indicates that the VALUE output holds the previously request-
ed read parameter value. This bit is set when USS_Drive_Control sees
the read response data from the drive. This bit is reset when either: you
request the response data using another USS_Read_Param poll, or on
the second of the next two calls to USS_Drive_Control.
Communication processor and Modbus TCP
13.4 Universal serial interface (USS) communication
Description
The USS_Read_Param instruction reads a parame-
ter from a drive. All USS functions associated with
one USS network and PtP communication port must
use the same data block. USS_Read_Param must
be called from a main program cycle OB.