hit counter script

Siemens SIMATIC S7-1200 System Manual page 1434

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Technical specifications
A.8 CPU 1217C
Technical data
Number of outputs on simultaneously 3 Solid state - MOSFET (sourcing) outputs (no adjacent points) and 4 differential
Cable length (meters)
Depending on your pulse receiver and cable, an additional load resistor (at least 10% of rated current) may improve
1
pulse signal quality and noise immunity.
Table A- 97
CPU 1217C Digital output (DQ) H/W configuration table
Output
Type and rate
DQa.0+ .0-
Type: RS422/RS485 differential output
Pulse train output rate: 1 MHz max., 2 Hz min.
DQa.1+ .1-
Type: RS422/RS485 differential output
Pulse train output rate: 1 MHz max., 2 Hz min.
DQa.2+ .2-
Type: RS422/RS485 differential output
Pulse train output rate: 1 MHz max., 2 Hz min.
DQa.3+ .3-
Type: RS422/RS485 differential output
Pulse train output rate: 1 MHz max., 2 Hz min.
DQa.4
Type: 24 V Sourcing output
Pulse train output rate: 100 kHz max., 2 Hz min.
DQa.5
Type: 24 V Sourcing output
Pulse train output rate: 100 kHz max., 2 Hz min.
DQa.6
Type: 24 V Sourcing output
Pulse train output rate: 100 kHz max., 2 Hz min.
DQa.7
Type: 24 V Sourcing output
Pulse train output rate: 100 kHz max., 2 Hz min.
DQb.0
Type: 24 V Sourcing output
Pulse train output rate: 100 kHz max., 2 Hz min.
DQb.1
Type: 24 V Sourcing output
Pulse train output rate: 100 kHz max., 2 Hz min.
1434
CPU 1217C DC/DC/DC
outputs at 60 °C horizontal or 50 °C vertical
10 at 55 °C horizontal or 45 °C vertical
500 m shielded, 150 m unshielded
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK

Advertisement

Table of Contents
loading

Table of Contents

Save PDF