Technical data
Isolation
RS485 signal to chassis ground
RS485 signal to CPU logic common
Cable length, shielded
Baud rate
Parity
Number of stop bits
Flow control
Wait time
Table A- 255 Power supply
Technical data
Power loss (dissipation)
From +5 V DC
Table A- 256 RS485 or RS422 connector (female)
Pin
Description
1
Logic or communication ground
2 TxD+
Connected for RS422
1
Not used for RS485: Output
3 TxD+
Signal B (RxD/TxD+): Input/Output
2
4 RTS
Request to send (TTL level) Output
3
5 GND
Logic or communication ground
Pin 2 (TxD+) and Pin 9 (TxD-) are the RS422 transmit signals.
1
Pin 3 (RxD/Tx+) and Pin 8 (RxD/TxD-) are RS485 transmit and receive signals. For RS422, Pin 3 is RxD+ and Pin 8 is
2
RxD-.
The RTS is a TTL level signal and can be used to control another half duplex device based on this signal. It is active
3
when you transmit and is inactive all other times.
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
A.17 TeleService (TS Adapter and TS Adapter modular)
CM 1241 RS422/485
707 V DC (type test)
1000 m max. (baud rate dependent)
300 baud, 600 baud, 1.2 kbits, 2.4 kbits, 4.8 kbits, 9.6 kbits (default),
19.2 kbits, 38.4 kbits, 57.6 kbits, 76.8 kbits, 115.2 kbits
No parity (default), even, odd, Mark (parity bit always set to 1),
Space (parity bit always set to 0)
1 (default), 2
XON/XOFF supported for the RS422 mode
0 to 65535 ms
CM 1241 RS422/485
1.1 W
220 mA
Connector
Pin
(female)
6 PWR
7
8 TXD-
2
9 TXD-
1
SHELL
Technical specifications
Description
+5 V with 100 ohm series resistor: Output
Not connected
Signal A (RxD/TxD-): Input/Output
Connected for RS422
Not used for RS485: Output
Chassis ground
1545