Model
Number of outputs on simultaneously
Cable length (meters)
Table A- 115 Wiring diagrams for the 8-point digital output SMs
SM 1222 DQ 8 x Relay
(6ES7222-1HF32-0XB0)
Table A- 116 Connector pin locations for SM 1222 DQ 8 x Relay (6ES7222-1HF32-0XB0)
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
SM 1222
DQ 16 x Relay
8 (no adjacent points) at 60 °C
horizontal or 50 °C vertical
16 at 55 °C horizontal or 45 °C
vertical
500 m shielded, 150 m unshielded
Pin
1
L+ / 24 V DC
2
M / 24 V DC
3
Functional Earth
4
1L
5
DQ a.0
6
DQ a.1
7
DQ a.2
A.9 Digital signal modules (SMs)
SM 1222
DQ 16 x 24 V DC
16
SM 1222 DQ 8 x 24 V DC
(6ES7222-1BF32-0XB0)
X10
No connection
2L
DQ a.3
DQ a.4
DQ a.5
DQ a.6
DQ a.7
Technical specifications
X11
1447