Technical specifications
Permitted ambient conditions
Ambient temperature
during storage
during transportation
during operation with a vertical installation (DIN rail hori-
zontal)
during operation with a horizontal installation (DIN rail
vertical)
Relative humidity at 25 °C during operation, without conden-
sation, maximum
Degree of protection
Power supply, current consumption and power loss
Type of power supply
Power supply / external
minimum
maximum
Current consumption (typical)
from 24 V DC
from the S7-1200 backplane bus
Effective power loss (typical)
from 24 V DC
from the S7-1200 backplane bus
24 V DC power supply
Min. cable cross section
Max. cable cross section
Tightening torque of the screw terminals
Electrical isolation
Power supply unit to internal circuit
Dimensions and weights
Width
Height
Depth
Weight
Net weight
Weight including packaging
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
-40 °C to 70 °C
-40 °C to 70 °C
0 °C to 55 °C
0 °C to 45 °C
95 %
IP20
DC
24 V
19.2 V
28.8 V
100 mA
0 mA
2.4 W
0 W
min.: 0.14 mm
(AWG 25)
2
max.: 1.5 mm
(AWG 15)
2
0.45 Nm (4 lb-in)
710 V DC for 1 minute
30 mm
100 mm
75 mm
133 g
170 g