hit counter script

Siemens SIMATIC S7-1200 System Manual page 1443

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Table A- 108 Wiring diagrams for the digital input SMs
SM 1221 DI 8 x 24 V DC (6ES7221-1BF32-
0XB0)
For sinking inputs, connect "-" to "M" (shown). For sourcing inputs, connect "+" to "M".
Table A- 109 Connector pin locations for SM 1221 DI 8 x 24 V DC (6ES7221-1BF32-0XB0)
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
Pin
1
Functional Earth
2
No connection
3
1M
4
DI a.0
5
DI a.1
6
DI a.2
7
DI a.3
A.9 Digital signal modules (SMs)
SM 1221 DI 16 x 24 V DC (6ES7221-1BH32-
0XB0)
X10
No connection
No connection
2M
DI a.4
DI a.5
DI a.6
DI a.7
Technical specifications
X11