hit counter script

Siemens SIMATIC S7-1200 System Manual page 1144

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Communication processor and Modbus TCP
13.3 Point-to-point (PtP) communication
Network 3: Enable the SEND_PTP instruction when the M20.0 flag is set. Also use this flag
to set the REQ input to TRUE for one scan. The REQ input tells the SEND_PTP instruction
that a new request is to be transmitted. The REQ input must only be set to TRUE for one
execution of SEND_PTP. The SEND_PTP instruction is executed every scan until the
transmit completes. The transmit is complete when the last byte of the message has been
transmitted from the CM 1241. When the transmit is complete, the DONE output (Tag_5 at
M10.0) is set TRUE for one execution of SEND_PTP.
Network 4: monitor the DONE output of SEND_PTP and reset the transmit flag (Tag_8 at
M20.0) when the transmit operation is complete. When the transmit flag is reset, the
RCV_PTP instruction in Network 1 is enabled to receive the next message.
1144
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK

Advertisement

Table of Contents
loading

Table of Contents

Save PDF