Parameter and type
AcknDelayTime
IN
BuildupAttempts IN
RepetitionAt-
IN
tempts
DONE
OUT
ERROR
OUT
STATUS
OUT
Table 13- 21 Condition codes
STATUS (W#16#....)
16#8380
16#8381
16#8382
16#8383
16#8384
16#8385
16#8386
16#8387
16#8388
16#8389
16#838A
16#838B
16#838C
16#838D
16#838E
16#838F
16#8391
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
Data type
Description
UInt
Acknowledgment delay time setting (depending on the set data transmission
rate) (default value: 2000 ms)
1 ms to 65535 ms
UInt
Number of connection attempts (default value: 6 connection attempts)
1 to 255
UInt
Number of transmission attempts (default value: 6 connection attempts)
1 to 255
Bool
TRUE for one execution after the last request was completed with no error
Bool
TRUE for one execution after the last request was completed with an error
Word
Execution condition code (Default value: 0)
Description
Parameter assignment error: Invalid value for "Character delay time".
Parameter assignment error: Invalid value for "Response timeout".
Parameter assignment error: Invalid value for "Priority".
Parameter assignment error: Invalid value for "Block check"
Parameter assignment error: Invalid value for "Connection attempts".
Parameter assignment error: Invalid value for "Transmission attempts".
Runtime error: Number of connection attempts exceeded
Runtime error: Number of transmission attempts exceeded
Runtime error: Error at the "Block check character"
The internally calculated value of the block check character does not correspond to the
block check character received by the partner at the connection end.
Runtime error: Invalid character received while waiting for free receive buffer
Runtime error: Logical error during receiving.
After DLE was received, a further random character (other than DLE or ETX) was re-
ceived.
Runtime error: Character delay time exceeded
Runtime error: Wait time for free receive buffer has started
Runtime error: frame repetition does not start within 4 s after NAK
Runtime error: In idle mode, one or several characters (other than NAK or STX) were
received.
Runtime error: Initialization conflict - Both partners have set high priority
Parameter assignment error: 3964 configuration data rejected because Freeport is set
Communication processor and Modbus TCP
13.3 Point-to-point (PtP) communication
1121