Technical specifications
A.7 CPU 1215C
Table A- 71
Power supply
Technical data
Voltage range
Line frequency
Input current
CPU only
(max. load)
CPU with all expansion
accessories
Inrush current (max.)
Isolation (input power to logic)
Ground leakage, AC line to functional
earth
Hold up time (loss of power)
Internal fuse, not user replaceable
Table A- 72
Sensor power
Technical data
Voltage range
Output current rating (max.)
Maximum ripple noise (<10 MHz)
Isolation (CPU logic to sensor power)
1414
CPU 1215C
CPU 1215C
AC/DC/Relay
DC/DC/Relay
85 to 264 V AC
20.4 V DC to 28.8 V DC
47 to 63 Hz
--
100 mA at 120 V AC
500 mA at 24 V DC
50 mA at 240 V AC
300 mA at 120 V AC
1500 mA at 24 V DC
150 mA at 240 V AC
20 A at 264 V AC
12 A at 28.8 V DC
1500 V AC
Not isolated
0.5 mA max.
-
20 ms at 120 V AC
10 ms at 24 V DC
80 ms at 240 V AC
3 A, 250 V, slow blow
CPU 1215C
AC/DC/Relay
20.4 to 28.8 V DC
400 mA (short-circuit protected)
< 1 V peak to peak
Not isolated
CPU 1215C
DC/DC/DC
CPU 1215C
CPU 1215C
DC/DC/Relay
DC/DC/DC
L+ minus 4 V DC min.
Same as input line