Technical specifications
A.9 Digital signal modules (SMs)
A.9.3

SM 1222 16-point digital output specifications

Table A- 113 General specifications
Model
Article number
Dimensions W x H x D (mm)
Weight
Power dissipation
Current consumption (SM Bus)
Current consumption (24 V DC)
Table A- 114 Digital outputs
Model
Number of outputs
Type
Voltage range
Logic 1 signal at max. current
Logic 0 signal with 10K Ω load
Current (max.)
Lamp load
ON state contact resistance
Leakage current per point
Surge current
Overload protection
Isolation (field side to logic)
Isolation groups
Current per common (max.)
Inductive clamp voltage
Switching delay
Maximum relay switching frequency
Lifetime mechanical (no load)
Lifetime contacts at rated load (N.O.
contact)
Behavior on RUN to STOP
1446
SM 1222 DQ 16 x Relay
6ES7222-1HH32-0XB0
45 x 100 x 75
260 grams
8.5 W
135 mA
11 mA / Relay coil used
SM 1222
DQ 16 x Relay
16
Relay, mechanical
5 to 30 V DC or 5 to 250 V AC
-
-
2.0 A
30 W DC/200 W AC
0.2 Ω max. when new
--
7 A with contacts closed
No
1500 V AC (coil to contact)
None (coil to logic)
4
10 A
-
10 ms max.
1 Hz
10,000,000 open/close cycles
100,000 open/close cycles
Last value or substitute value (default
value 0)
SM 1222 DQ 16 x 24 V DC
6ES7222-1BH32-0XB0
45 x 100 x 75
220 grams
2.5 W
140 mA
100 mA
SM 1222
DQ 16 x 24 V DC
16
Solid state - MOSFET (sourcing)
20.4 to 28.8 V DC
20 V DC min.
0.1 V DC max.
0.5 A
5 W
0.6 Ω max.
10 μA max.
8 A for 100 ms max.
707 V DC (type test)
1
8 A
L+ minus 48 V, 1 W dissipation
50 μs max. off to on
200 μs max. on to off
-
-
-
Last value or substitute value (default
value 0)