hit counter script

Siemens SIMATIC S7-1200 System Manual page 1367

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

DC Outputs
Short -circuit protection circuitry is not provided for DC outputs on CPUs, signal modules
(SMs) and signal boards (SBs).
Relay electrical service life
The typical performance data estimated from sample tests is shown below. Actual
performance may vary depending upon your specific application. An external protection
circuit that is adapted to the load will enhance the service life of the contacts. N.C. contacts
have a typical service life of about one-third that of the N.O. contact under inductive and
lamp load conditions.
An external protective circuit will increase the service life of the contacts.
Table A- 8
Data for selecting an actuator
Continuous thermal current
Switching capacity and life of the contacts
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
Typical performance data
For ohmic load
For inductive load (according to
IEC 947-5-1 DC13/AC15)
A.2 General technical specifications
2 A max.
Voltage
Current Number of operating cycles
(typical)
24 V DC
2.0 A
0.1 million
24 V DC
1.0 A
0.2 million
24 V DC
0.5 A
1.0 million
48 V AC
1.5 A
1.5 million
60 V AC
1.5 A
1.5 million
120 V
2.0 A
1.0 million
AC
120 V
1.0 A
1.5 million
AC
120 V
0.5 A
2.0 million
AC
230 V
2.0 A
1.0 million
AC
230 V
1.0 A
1.5 million
AC
230 V
0.5 A
2.0 million
AC
Voltage
Current Number of operating cycles
(typical)
24 V DC
2.0 A
0.05 million
24 V DC
1.0 A
0.1 million
24 V DC
0.5 A
0.5 million
24 V AC
1.5 A
1.0 million
48 V AC
1.5 A
1.0 million
60 V AC
1.5 A
1.0 million
120 V
2.0 A
0.7 million
AC
Technical specifications
1367

Advertisement

Table of Contents
loading

Table of Contents

Save PDF