Communication processor and Modbus TCP
13.3 Point-to-point (PtP) communication
Table 13- 24 Condition codes
STATUS (W#16#....)
81D0
81D1
81D2
81D3
81D5
81D6
81D7
81D8
81DF
8281
8282
8301
8322
8324
8328
8332
833A
Note
Setting the maximum record length for Profibus communication
When using a CM1243-5 Profibus Master module to control an ET 200SP or ET 200MP
Profibus device that uses an RS232, RS422, or RS485 point-to-point module, you need to
explicitly set the "max_record_len" data block tag to 240 as defined below:
Set "max_record_len" in the instance DB (for example, "Send_P2P_DB".max_record_len) to
240 after running any configuration instruction such as Port_Config, Send_Config, or
Receive_Config.
Explicitly assigning max_record_len is only necessary with Profibus communication; Profinet
communication already uses a valid max_record_len value.
1124
Description
New request while transmitter active
Transmit aborted because of no CTS within wait time
Transmit aborted because of no DSR from the DCE device
Transmit aborted because of queue overflow (transmit more than 1024 bytes)
Reverse bias signal (wire break condition)
Transmission request rejected because end delimiter was not found in the transmit buffer
Internal error / error in synchronization between FB and CM
Transmission attempt rejected because the port has not been configured
CM has reset the interface to the FB due to one of the following reasons
The module has restarted (Power cycle)
The CPU has reached a breakpoint
The module has been reparameterized
In each case the module indicates this code in the Status parameter. The module resets
Status and Error to zero after the first received record for SEND_P2P.
Negative acknowledgement while writing the module
DP slave or module not available
Illegal syntax ID at an ANY pointer
Range length error when reading a parameter
Range error when reading a parameter
Alignment error when reading a parameter
The parameter contains a DB number that is higher than the highest permitted number (DB
number error).
The DB for the BUFFER parameter does not exist.
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK