Message end conditions
You also configure how the communication interface recognizes the end of a message. You
can configure multiple message end conditions. If any one of the configured conditions
occurs, the message ends.
For example, you could specify an end condition with an end of message timeout of 300
milliseconds, an inter-character timeout of 40 bit times, and a maximum length of 50 bytes.
The message will end if the message takes longer than 300 milliseconds to receive, or if the
gap between any two characters exceeds 40 bit times, or if 50 bytes are received.
Parameter
Recognize message end by
message timeout
Recognize message end by
response timeout
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
Definition
The message end occurs when the configured amount of time to wait for the message end
has expired. The message timeout period begins when a start condition has been satisfied.
The default is 200 ms and the range is 0 to 65535 ms.
Received characters
Start Message condition satisfied: message timer starts
Message timer expires and terminates the message
The message end occurs when the configured amount of time to wait for a response ex-
pires before a valid start sequence is received. The response timeout period begins when a
transmission ends and the CM or CB begins the receive operation. The default response
timeout is 200 ms and the range is 0 to 65535 ms. If a character is not received within the
response time period, RCVTIME, then an error is returned to the corresponding RCV_PTP
instruction. The response timeout does not define a specific end condition. It only specifies
that a character must be successfully received within the specified time. You must config-
ure another end condition to indicate the actual end of a message.
Transmitted characters
Received characters
First character must be successfully received by this time.
Communication processor and Modbus TCP
13.3 Point-to-point (PtP) communication