Table 13- 148 Data types for the parameters
Parameter and type
REQ
IN
MB_ADDR
IN
MODE
IN
DATA_ADDR
IN
DATA_LEN
IN
DATA_PTR
IN
DONE
OUT
BUSY
OUT
ERROR
OUT
STATUS
OUT
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
13.9 Legacy Modbus RTU communication (CM/CB 1241 only)
Data type
Description
Bool
0=No request
1= Request to transmit data to Modbus slave
V1.0: USInt
Modbus RTU station address:
V2.0: UInt
Standard addressing range (1 to 247)
Extended addressing range (1 to 65535)
The value of 0 is reserved for broadcasting a message to all Modbus
slaves. Modbus function codes 05, 06, 15 and 16 are the only function
codes supported for broadcast.
USInt
Mode Selection: Specifies the type of request (read, write, or diagnostic).
See the Modbus functions table below for details.
UDInt
Starting Address in the slave: Specifies the starting address of the data to
be accessed in the Modbus slave. See the Modbus functions table below
for valid addresses.
UInt
Data Length: Specifies the number of bits or words to be accessed in this
request. See the Modbus functions table below for valid lengths.
Variant
Data Pointer: Points to the M or DB address (non-optimized DB type) for
the data being written or read.
Bool
The DONE bit is TRUE for one scan, after the last request was completed
with no error.
Bool
0 – No MB_MASTER operation in progress
1 – MB_MASTER operation in progress
Bool
The ERROR bit is TRUE for one scan, after the last request was termi-
nated with an error. The error code value at the STATUS parameter is
valid only during the single scan where ERROR = TRUE.
Word
Execution condition code
Communication processor and Modbus TCP
1273