UM353-1
4.2 FCO102 - Single Loop Controller w/ Fixed Setpoint
Factory Configured Option FCO102 provides a single loop controller configured in Loop01. A block diagram of
the loop configuration is shown below along with any changes to the default parameter values of the configured
blocks. If the loop tag 'Loop01' is changed, all configured references within the station will automatically be
changed to the new tag.
TV
SETPT
TC
SR
LU
LD
Process
O1
AIN1
QS
.
P
D
ALARM
SETPT - Setpoint Function Block
RG PTR - Range Pointer ----------- Loop01.AIN1.OR
ESN - Exec. Seq. No.--------------- 5
ALARM - Alarm Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
INPUT P - Input P ----------------- Loop01.AIN1.O1
INPUT D - Input D ---------------- Loop01.SETPT.O1
ESN - Exec. Seq. No. ------------- 10
PID - PID Controller Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
INPUT P - Input P ----------------- Loop01.AIN1.O1
INPUT S - Input S ----------------- Loop01.SETPT.O1
INPUT F - Input F ----------------- Loop01.A/M.O1
INPUT A - Input A ---------------- Loop01.A/M.AS
ESN - Exec. Seq. No.-------------- 15
March 2003
O1
S
P
S
F
P
A
I
A1
A2
A3
A4
A/M - Auto/Manual Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT A - Input A ------------------ Loop01.PID.O1
ESN - Exec. Seq. No. ---------------- 20
AOUT1 - Analog Output 1 Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT S - Input S ------------------- Loop01.A/M.O1
ODC - Operator Display for Controllers
P RG PTR - P Range Pointer ------- Loop01.AIN1.OR
V RG PTR - V Range Pointer ------ Loop01.PID.OR
INPUT P - Input P (Process) ------- Loop01.AIN1.O1
INPUT S - Input S (Setpoint) ------ Loop01.SETPT.O1
INPUT V - Input V (Valve) -------- Loop01.A/M.O1
LOOP # - Loop # ------- 01
Factory Configured Options
O1
A
O1
PID
AE
TV
AS
A/M
AW
TC
NA
EM
MS
ES
SS
Valve
S
AOUT1
D
QS
.
V
LOOP01
4-3