Factory Configured Options

4.4 FCO104 - External Set Controller with Non-Tracking Local Setpoint

Factory Configured Option FCO104 provides a single loop controller with external setpoint configured in Loop01.
A block diagram of the loop configuration is shown below along with any changes to the default parameter values
of the configured blocks. If the loop tag 'LOOP01' is changed, all configured references will automatically be
changed to the new tag.
External Setpoint
0.00-100.00 PRCT
O1
AIN2
QS
TV
SETPT
TC
SR
LU
LD
Process
0.00-100.00 PRCT
0.00-100.00 PRCT
O1
AIN1
QS
IRev. 2)
PB2SW - PB2 Switch Function Block
INPUT MD - Input MD ------- Loop01.E/I.SE
ESN - Exec. Seq. No. ---------- 5
ALARM - Alarm Function Block
RG PTR - Range Pointer ------- Loop01.AIN1.OR
INPUT P - Input P -------------- Loop01.AIN1.O1
INPUT D - Input D ------------- Loop01.E/I.O1
ESN - Exec. Seq. No. ---------- 20
PID - PID Controller Function Block
RG PTR - Range Pointer ----------- Loop01.AIN1.OR
INPUT P - Input P ------------------ Loop01.AIN1.O1
INPUT S - Input S ------------------ Loop01.E/I.O1
INPUT F - Input F ------------------ Loop01.A/M.O1
INPUT A - Input A ----------------- Loop01.A/M.AS
INPUT I - Input I ------------------- Loop01.E/I.ES
ESN - Exec. Seq. No.--------------- 25
4-6
X
NC
NO
PB2SW
PS
MD
ST
E
E/I
O1
I
IO
P
PID
S
F
P
A
I
E/I - Ext/Int Transfer Switch Function Block
INPUT ST - Input ST -------------- Loop01.PB2SW.PS
INPUT E - Input E ------------------ Loop01.AIN2.O1
INPUT I - Input I ------------------- Loop01.SETPT.O1
ESN - Exec. Seq. No. -------------- 15
A/M - Auto/Manual Function Block
RG PTR - Range Pointer ---------- Loop01.PID.OR
INPUT A - Input A ----------------- Loop01.PID.O1
ESN - Exec. Seq. No. -------------- 30
SETPT - Setpoint Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
ESN - Exec. Seq. No. -------------- 10
AOUT1 - Analog Output 1 Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT S - Input S ------------------- Loop01.A/M.O1
A1
P
A2
D
ALARM
A3
A4
O1
S
SE
SI
IS
ES
O1
A
O1
S
AOUT1
AE
TV
AS
D
A/M
AW
TC
NA
QS
EM
MS
ES
SS
V
UM353-1
S
DOUT1
S
DOUT2
Valve
LOOP01
March 2003