Factory Configured Options
Primary Loop (cont)
ALARM - Alarm Function Block
RG PTR - Range Pointer -------- PRIM.AIN1.OR
INPUT P - Input P --------------- PRIM.AIN1.O1
INPUT D - Input D -------------- PRIM.SPLIM.O1
ESN - Exec. Seq. No. ----------- 20
PID - PID Controller Function Block
RG PTR - Range Pointer -------- PRIM.AIN1.OR
INPUT P - Input P --------------- PRIM.AIN1.O1
INPUT S - Input S --------------- PRIM.SPLIM.O1
INPUT F - Input F --------------- SEC.AIN02.O1
INPUT A - Input A -------------- PRIM.A/M.AS
ESN - Exec. Seq. No.------------ 30
A/M - Auto/Manual Function Block
RG PTR - Range Pointer -------- PRIM.PID.OR
INPUT A - Input A --------------- PRIM.PID.O1
INPUT TV - Input TV ----------- SEC.AIN2.O1
INPUT TC - Input TC ----------- SEC.OR01.O1
ESN - Exec. Seq. No. ----------- 60
ODC - Operator Display for Controllers
P RG PTR - P Range Pointer ------ PRIM.AIN1.OR
V RG PTR - V Range Pointer ----- PRIM.PID.OR
INPUT P - Input P (Process) ------ PRIM.AIN1.O1
INPUT S - Input S (Setpoint) ----- PRIM.SPLIM.O1
INPUT V - Input V (Valve) ------- PRIM.A/M.O1
LOOP # - Loop # ------ 01
Secondary Loop
SETPT - Setpoint Function Block
RG PTR - Range Pointer -------- SEC.AIN2.OR
INPUT TV - Input TV ---------- SEC.AIN2.O1
INPUT TC - Input TC ---------- SEC.OR02.O1
INPUT LU - Input LU --------- SEC.SPLIM.HS
INPUT LD - Input LD --------- SEC.SPLIM.LS
ESN - Exec. Seq. No.----------- 5
ALARM - Alarm Function Block
RG PTR - Range Pointer ------ SEC.AIN2.OR
INPUT P - Input P ------------- SEC.AIN2.O1
INPUT D - Input D ------------ SEC.SPLIM.O1
ESN - Exec. Seq. No. --------- 10
PB2SW - PB2 Switch Function Block
INPUT MD - Input MD ------- SEC.E/I.SE
ESN - Exec. Seq. No. --------- 15
4-16
E/I - Ext/Int Transfer Switch Function Block
INPUT ST - Input ST --------- SEC.PB2SW.PS
INPUT E - Input E ------------ PRIM.A/M.O1
INPUT I - Input I -------------- SEC.SETPT.O1
ESN - Exec. Seq. No. --------- 20
SPLIM - Setpoint Limit Function Block
RG PTR - Range Pointer ------ SEC.AIN2.OR
INPUT A - Input A ------------ SEC.E/I.O1
ESN - Exec. Seq. No. --------- 25
PID - PID Controller Function Block
RG PTR - Range Pointer -------- SEC.AIN2.OR
INPUT P - Input P --------------- SEC.AIN2.O1
INPUT S - Input S --------------- SEC.SPLIM.O1
INPUT F - Input F --------------- SEC.A/M.O1
INPUT A - Input A -------------- SEC.A/M.AS
INPUT I - Input I ---------------- SEC.E/I.ES
ESN - Exec. Seq. No.------------ 30
A/M - Auto/Manual Function Block
RG PTR - Range Pointer ---------- SEC.PID.OR
INPUT A - Input A ----------------- SEC.PID.O1
ESN - Exec. Seq. No. ------------- 35
OR01 - OR Function Block
INPUT A - Input A -------------- SEC.A/M.NA
INPUT B - Input B -------------- SEC.E/I.IS
ESN - Exec. Seq. No. ----------- 40
OR02 - OR Function Block
INPUT A - Input A -------------- SEC.A/M.NA
INPUT B - Input B -------------- SEC.E/I.ES
ESN - Exec. Seq. No. ----------- 45
AOUT1 - Analog Output 1 Function Block
RG PTR - Range Pointer ----------- SEC.PID.OR
INPUT S - Input S ------------------ SEC.A/M.O1
ODC - Operator Display for Controllers
P RG PTR - P Range Pointer ---- SEC.AIN2.OR
V RG PTR - V Range Pointer -- SEC.PID.OR
INPUT P - Input P (Process) ----- SEC.AIN2.O1
INPUT S - Input S (Setpoint) ---- SEC.SPLIM.O1
INPUT V - Input V (Valve) ------ SEC.A/M.O1
LOOP # - Loop# ----- 02