hit counter script

Configuration Data Sequencer Loop - Siemens Moore 353 User Manual

Process automation controller
Table of Contents

Advertisement

Data Mapping

7.3.13 Configuration Data Sequencer Loop

The Modbus registers or LIL parameters on this page refer to configuration parameters of function blocks within a
specific loop previously defined by Modbus parameter MSLCP (40048) or LIL parameter LSLCP (7/1). For
example, to read or write the Step 1 Group 0 Input Mask for the PRSEQ block that is in a loop with a Modbus Index
of 3, write a 3 to 40048, then read or write to register 410001.
Sequencer (MASK Configurations)
Code
`R/W
Description
S001G0I
R/W
Step 1 Group 0 Input Mask
S001G0O
R/W
Step 1 Group 0 Output Mask
S001G1I
R/W
Step 1 Group 1 Input Mask
S001G1O
R/W
Step 1 Group 1 Output Mask
S001G2I
R/W
Step 1 Group 2 Input Mask
S001G2O
R/W
Step 1 Group 2 Output Mask
S001G3I
R/W
Step 1 Group 3 Input Mask
S001G3O
R/W
Step 1 Group 3 Output Mask
.........................................................................................................................................................................................
S250GEI
R/W
Step 250 Group E Input Mask
S250GEO
R/W
Step 250 Group E Output Mask
S250GFI
R/W
Step 250 Group F Input Mask
S250GFO
R/W
Step 250 Group F Output Mask
Real TimeTrip Block Configurations
Code
R/W
Description
RTT01Y
R/W
Year
RTT01M
R/W
Month
RTT01D
R/W
Day
RTT01HR
R/W
Hour
RTT01MN
R/W
Minute
RTT01SC
R/W
Second
RTT01DA
R/W
Day
RTT02Y
R/W
Year
RTT02M
R/W
Month
RTT02D
R/W
Day
RTT02HR
R/W
Hour
RTT02MN
R/W
Minute
RTT02SC
R/W
Second
RTT02DA
R/W
Day
RTT03Y
R/W
Year
RTT03M
R/W
Month
RTT03D
R/W
Day
RTT03HR
R/W
Hour
RTT03MN
R/W
Minute
RTT03SC
R/W
Second
RTT03DA
R/W
Day
7-46
Range
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
$0000-$FFFF
Range
1999-
1-12
1-31
0-23
0-59
0-59
0000 0000 0SMT WTFS
1999-
1-12
1-31
0-23
0-59
0-59
0000 0000 0SMT WTFS
1999-
1-12
1-31
0-23
0-59
0-59
0000 0000 0SMT WTFS
Register (MB)
C/P (LIL)
410001
1/154
410002
1/170
410003
1/155
410004
1/171
410005
1/156
410006
1/172
410007
1/157
410008
1/173
417997
250/168
417998
250/184
417999
250/169
418000
250/185
Register (MB)
C/P (LIL)
419001
1/100 V 2.0
419002
1/101 V 2.0
419003
1/102 V 2.0
419004
1/103 V 2.0
419005
1/104 V 2.0
419006
1/105 V 2.0
419007
1/106 V 2.0
419008
2/100 V 2.0
419009
2/101 V 2.0
419010
2/102 V 2.0
419011
2/103 V 2.0
419012
2/104 V 2.0
419013
2/105 V 2.0
419014
2/106 V 2.0
419015
3/100 V 2.0
419016
3/101 V 2.0
419017
3/102 V 2.0
419018
3/103 V 2.0
419019
3/104 V 2.0
419020
3/105 V 2.0
419021
3/106 V 2.0
UM353-1