UM353-1
Wire Selection - Stranded wire is recommended for most connections, however, solid wire is typically used for
thermocouple extension wire. Carefully select wire size, conductor material, and insulation. Some selection
considerations are:
•
current and voltage to be carried
•
total length of each wire run
•
whether wire will be bundled or run singly
•
indoor or outdoor installation
•
temperature extremes (Use supply wires suitable for 5°C (10°F) above ambient temperature.)
•
exposure to sunlight
•
vibration
•
types of contaminates
Station Common, Terminal 6 - Within the Moore 353, station common is connected to:
•
the two-wire power supply common (COM, terminal 6)
•
digital output common (DOUTC, terminal 9)
•
all analog input and analog output commons (e.g., AIN1C, terminal 21)
Station common is isolated from case/safety ground. It should be connected to the user's instrument bus common at
only one point. Digital input commons are isolated from the station common and case/safety ground.
Connector Terminal and Ground Screw Torque Specifications:
•
connector terminals - 5 in. lbs (0.56 N m)
•
green case/safety ground screw - 20 in. lbs (2.26 N m)
Crimp-On (solderless) Connectors - A pin-style crimp-on connector can be used when two or more wires or a
combination of wires and component leads are to be inserted into a connector terminal at the rear of the case. Wires
and leads are crimped in the connector and the connector pin inserted in the
selected connector terminal. The connector can provide a more secure
connection when multiple leads are involved. An example of its use is shown at
right. Several crimp-on connectors are provided in various Moore 353
installation kits, and they are available from most electrical supply sources.
Wire Routing and Conduit - DC wiring should be separated from AC wiring and away from AC powered
pushbuttons, alarms, annunciators, motors, solenoids, and similar devices. Conduit and raceways are commonly
used for routing panel wiring. Wiring not installed in conduit or raceway should be clamped or supported
approximately every 12 inches (300 mm).
March 2003
Installation
Crimp-On
Signal Input Wire
Connector
Range Resistor