Maintenance
O-Ring Gasket
Keypad
Connector (2)
Part Number
Serial Number
Mounting Screw,
2 Places
INSTALLATION
1. Place an anti-static wrist strap on your wrist and connect the ground lead.
2. Get the replacement bezel, or get the replacement circuit board and remove it from the anti-static
bag.
3. If the bezel is being replaced, start threading each Faceplate mounting screw into the bezel. Use a screwdriver
to complete screw installation. Install the flip-down door; see the figure.
4. Turn the bezel over.
5. Install the circuit board in the bezel by slightly inserting the top edge of board under the Fixed Retainer. The
top edge is nearest the Numeric and Alphanumeric Displays.
6. Continue to ease the board under the Fixed Retainer while lowering the bottom edge of the board into the bezel.
Be sure that the keypad connector mates with the connector on the keypad. The board is fully inserted when it
snaps under the Flexible Retainer.
7. Install the Display Assembly on the case as described above.

11.5.3 MPU Controller Board

This board has a lithium battery; refer to Section 11.2.4 Board Handling Precautions. When replacing an MPU
Controller board, configuration parameters must be re-entered. Refer to Sections 2 and 3 and to Section 12
Calibration as needed. Factory repaired controllers must also be configured.
To replace the MPU Controller board or the station fuse use the following procedure:
REMOVAL:
1. Remove input power from Controller.
2. Remove Display Assembly as described in previous section.
3. If present, disconnect the Ethernet cable from J4 on the Ethernet board.
4. Grasp the loop in the front edge of the MPU Controller board and pull the board straight out of the case.
If the board is to be shipped or stored, compare the board at hand to Figures 11-
2 and 11-3 and set W7 or W8 as shown in the appropriate figure.
5. Remove any installed accessory boards; refer to Section 11.5.5 and Figure 11-5.
11-14
Fixed Board Retainer
Numeric Display (2)
Alphanumeric Display (2)
Connector
Notes:
(1) - Grasp at this point
when removing board.
(2) - On other side of
(1)
(1)
board.
(3) - Press to remove and
install door.
Flexible Board Retainer
Foam
Rear View
NOTE
UM353-1
Side
View
Flip-Down
Door
(3)