hit counter script

Environmental Specifications; Standard Mounting; Enclosure Mounting; Electromagnetic Compatibility (Emc) - Siemens Moore 353 User Manual

Process automation controller
Table of Contents

Advertisement

UM353-1

14.9 ENVIRONMENTAL SPECIFICATIONS

14.9.1 Standard Mounting

Mounting, Typical Location ........................................Control room or other protected area
Temperature Limits:
Operating.......................................................0 to 50°C (32 to 122°F)
Storage ..........................................................-40 to 85°C (-40 to 185°F)
Climatic Conditions.....................................................IEC654-1 (Class B3)
Corrosive Conditions...................................................IEC 654-4 (Class 2)

14.9.2 Enclosure Mounting

Mounting:
Typical Location ...........................................Out-of-doors or other area without environmental controls
Enclosure.......................................................User supplied
Model 353 Case.............................................Installed inside enclosure
Model 353 Display........................................Exposed through enclosure to external environment
Installation Requirements..............................Refer to Section 8 Installation
Temperature Limits:
Enclosure Internal, Operating .......................0 to 50°C (32 to 122°F)
Enclosure External, Operating ......................-40 to 50°C (-40 to 122°F)
Controller Storage .........................................-40 to 85°C (-40 to 185°F)
Climatic Conditions:....................................................IEC654-1 (Class B3)
Corrosive Conditions:..................................................IEC654-4 (Class 2)

14.9.3 Electromagnetic Compatibility (EMC)

EN61326-1, 1998
EN50081-2 (Radiated Emissions)
EN55011 (Conducted Emissions)
EN61000-3-2 (Flicker)
EN61000-3-3 (Current Harmonics)
EN61000-4-2 (ESD)

14.10 AGENCY APPROVALS

The Moore 353 has been designed to meet various agency approvals. Contact the factory or your local Siemens
(Process Industries Division) representative for current approvals. Labels on each Moore 353 list the agency
approvals that apply to that particular instrument.
FM/CSA
Class I, Division 2, Groups A, B, C, and D
CE - see Section 14.10.2
ABS TYPE Approval
March 2003
Model Designation and Specifications
EN61000-4-3 (EM Field)
EN61000-4-4 (EFT/Burst)
EN61000-4-5 (Surge)
EN61000-4-6 (Conducted RF)
EN61000-4-8 (Magnetic Immunity)
EN61000-4-11 (Voltage Dip/Short Interruption)
14-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents