UM353-1
6. Place the MPU Controller board in a static shielding bag.
INSTALLATION:
1. While wearing a grounded wrist strap, remove MPU Controller board from static shielding bag.
2. Check and change jumper settings as needed. See Figures 11-2 and 11-3 for jumper locations and set W7 or
W8 as shown. Set W2 and W4 as described in Section 11.5.5 Accessory Boards.
3. Fasten needed accessory boards to the MPU Controller board. Refer to Section 11.5.5.
4. Insert the MPU Controller board into the case and carefully guide the connector end of the board until it mates
with the connector at the back of the case. Only when the connectors are mated should additional force be
applied to seat the board.
5. If an Ethernet board is installed, connect the free end of the Ethernet cable, from inside the case, to the Ethernet
connector J4 on the board. See Section 11.5.6 as necessary.
6. Disconnect wrist strap.
7. Install Display Assembly as described in the previous section.

11.5.4 I/O Expander Board

REMOVAL:
1. In a hazardous area, remove input power from Controller.
2. Remove Display Assembly and MPU Controller board as described in previous sections.
3. Refer to Figure 11-4. Grasp the edge of the I/O Expander Board and pull the Board straight out of the case.
4. Place the Board in a static shielding bag.
INSTALLATION
1. While wearing a grounded wrist strap, remove the I/O Expander Board from its static shielding bag.
2. If one or more communication boards must be attached to the MPU Controller board, refer to the Accessory
Board section and then return here.
3. Insert the I/O Expander Board into the case and carefully guide the connector end of the board until it mates
with the connector at the back of the case. Only when the connectors are mated should additional force be
applied to seat the board.
4. Disconnect wrist strap.
5. Install MPU Controller board and Display Assembly as described in previous sections.
After replacing an I/O Expander board in a controller whose configuration includes an
AINU function block: assemble the controller, apply power, ENTER configuration and
STORE the SEN TYPE parameter. This must be done even if the SEN TYPE displays
the desired type. This will ensure that the function block loads the correct calibration
from the new Expander board. If desired, a FIELD CAL can then be performed.