Error Codes - Siemens Moore 353 User Manual

Process automation controller
Table of Contents

Advertisement

UM353-1
W2 LIL/Modbus Network Jumper (Rear Terminals 3 & 4)
F1
P1
Jumpers are factory set for the
circuit boards installed at time of
shipment.
Available jumpers may vary with
board version.
W4 LonWorks I/O Bus (Rear Terminals 25 & 26)
FIGURE 11-3 MPU Controller Board with RTC Jumper W7

11.4 ERROR CODES

This section describes off-line error codes, on-line error codes, and on-line status codes. Typically, a code will
point to a failed internal assembly or a failed peripheral device. Note that a configuration error can also cause an
error code or multiple error codes to be produced.
OFF-LINE ERROR CODES
Off-line error messages are displayed while the 353 is powered but not running function block code and therefore
not actively controlling a process. Depending on the message, user intervention will most likely be required.
Corrective action can be initiated via the LIL or Modbus ports if appropriate. LIL parameter "SE" located at
channel 4, parameter 1 (Modbus register 40002) will contain the hexadecimal form of the error number currently
displayed (e.g., ERR: 213 would be sent as $00D5). An Error message can be acknowledged over the network by
writing a 0 to the Modbus register or LIL parameter. Messages are displayed one at a time, in order of occurrence,
and a message cannot be cleared until the error condition is corrected.
March 2003
C69
U11
T2
W7 Real Time Clock
MPU Board Storage
and Cold Start
Battery
W7 Real Time Clock Jumper
1. Place Shunt On Both Pins To
Enable Hot/Warm Start.
2. Place Shunt On One Pin When
Storing Controller Or MPU
Controller Board.
P4
W6 Hardware Watchdog
Timer Control, Factory Set
J3
J6
J5
P2
X03152S3
Hot / Warm Start
Enabled
Maintenance
Connects To
Display
Assembly
Kernel Jumper - Pads
on top and bottom
of board.
11-7