UM353-1
Suggested Actions
4. When upgrading MPU Controller firmware:
1) Generate a report of all network bindings.
2) Uninstall the controller node from a network.
3) Upgrade the controller firmware
4) Install the controller node.
5) Refer to the above report and bind all network variables.
If the controller has already been upgraded, it can still be uninstalled with the current
version of the MetaVision 3.0x Network Manager but uninstalling prior to upgrading is
recommended. Other Network Managers may not allow this.
5. Once a LonWorks option board is used in a 1.30 or higher controller and is uninstalled and removed from
service, mark the board as "1.30 firmware only".
March 2003
Note
LonWorks Communications
5-3