Receive_Reset (Delete Receive Buffer) - Siemens SIMATIC S7-1200 System Manual

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Communication processor and Modbus TCP
13.3 Point-to-point (PtP) communication
13.3.5.8

Receive_Reset (Delete receive buffer)

Table 13- 29 Receive_Reset (Receiver Reset) instruction
LAD / FBD
STEP 7 automatically creates the DB when you insert the instruction.
1
Table 13- 30 Data types for parameters
Parameter and type
REQ
IN
PORT
IN
DONE
OUT
ERROR
OUT
STATUS
OUT
1128
SCL
"Receive_Reset_DB"(
REQ:=_bool_in_,
PORT:=_word_in_,
DONE=>_bool_out_,
ERROR=>_bool_out_,
STATUS=>_word_out_);
Data type
Description
Bool
Activates the receiver reset on the rising edge of this enable input (Default
value: False)
PORT
After you install and configure a CM or CB communication device, the port
identifier appears in the parameter helper drop-list available at the PORT box
connection. The assigned CM or CB port value is the device configuration
property "hardware identifier". The port symbolic name is assigned in the "Sys-
tem constants" tab of the PLC tag table. (Default value: 0)
Bool
When TRUE for one scan, indicates that the last request was completed with-
out errors.
Bool
When TRUE, shows that the last request was completed with errors. Also,
when this output is TRUE, the STATUS output will contain related error codes.
Word
Error code (Default value: 0)
Description
Receive_Reset clears the receive
buffers in the CM or CB.
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK