Legacy Modbus Tcp Examples; Example: Legacy Mb_Server Multiple Tcp Connections - Siemens SIMATIC S7-1200 System Manual

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Communication processor and Modbus TCP
13.8 Legacy Modbus TCP communication
13.8.4

Legacy Modbus TCP examples

13.8.4.1

Example: Legacy MB_SERVER Multiple TCP connections

You can have multiple Modbus TCP server connections. To accomplish this, MB_SERVER
must be independently executed for each connection. Each connection must use an
independent instance DB, connection ID, and IP port. The S7-1200 allows only one
connection per IP port.
For best performance, MB_SERVER should be executed every program cycle, for each
connection.
Network 1: Connection #1 with independent IP_PORT, connection ID, and instance DB
Network 2: Connection #2 with independent IP_PORT, connection ID, and instance DB
1264
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK