Siemens SIMATIC S7-1200 System Manual page 1328

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Online and diagnostic tools
15.13 Monitoring and modifying values in the CPU
Copying the snapshot values to the CPU
To copy the snapshot values to the actual values of the data block tags in the CPU, click the
following button:
The online CPU loads the snapshot values into the actual values. The Monitor value column
shows the actual values in the CPU. The scan cycle might subsequently change the values
in the CPU from the snapshot values, but at the time you make the copy, the CPU loads the
snapshot values in a consistent download.
Note
Be aware that if your snapshot contains state information, timer values, or calculated
information, the CPU restores those values as of the time you made the snapshot.
Copying the snapshot values to the start values
To copy the snapshot values to the start values of the data block tags, click the following
button:
After you compile the DB and download it to the CPU, the DB uses the new start values
when the CPU goes to RUN mode.
Copying individual snapshot or monitor values to start values
The data block editor also lets you copy individual values and paste them over start values.
Simply right-click a value in any value column and select Copy to place it in the Windows
clipboard. Then, you can right-click on any start value and select paste to replace that value
with the value in the clipboard.
After you compile the DB and download it to the CPU, the DB uses the new start values
when the CPU goes to RUN mode.
1328
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK